 |
110 A Circuit Breaker
240V 110A breaker feeds LAN rooms.
Load Reading A=65 B=95 N=84
B phase exceeds 80% ampacity and temperature exceeds breaker rating.
|
 |
32 Gallon Drum
The thermogram documents the dramatic level of heat being generated by the exothermic reaction of sodium hydrosulfite and water in a 32 gallon drum.
|
 |
A/C Unit Problem
A\C unit overheated and shut down after running for aproximately 30 min. After visual inspection from ground level maintenance was unable to ...more
|
 |
Acid Tank Levels
Infrared Thermography is a SAFE and effective way to verify, or check acid tank levels. Infrared can also be used on various other liquid, and solids ...more
|
 |
Asphalt paving
The thermograph shows the contrast in temperatures between the cool, curing lane to the right (113.3°F) and the hot mat being laid down on the left ...more
|
 |
Belt Drive
Note high temperatures present in the left thermogram. Second thermogram presumably after repair or alignment.
|
 |
Bolted Bus Connecion
Hot bolted bus bar connection.
|
 |
Breaker Connection
Internal breaker connection problem.
|
 |
Breaker connection on a boat
Bad breaker connection on main panel of a large boat. This is a serious problem that is hard to see. The infrared scan instantly reveals and ...more
|
 |
Bus-breaker
A bad bus-breaker connection.
|
 |
Bushing connection
An overheating bushing connection
|
 |
Buss Assembly
FURNACE BUSS ASSEMBLY IN MAIN TRANSFORMER VAULT WHERE IT CONNECTS TO TRANSFORMER.
The thermogram shows a hot spot on the third bar from the ...more
|
 |
Cable to Busbar Connection
This cable to busbar connection feeding a pump is excessively hot and needs attention.
|
 |
Circuit Breaker
Hot lug connection.
|
 |
Circuit Breaker Panel
Note how thermography easily finds the problems in this circuit breaker panel.
|
 |
Circuit protector
Bolted connection problem on a circuit switcher.
|
 |
Connection in a substation
This thermal image shows a hot connection—measuring 437°F when viewed with a telescope lens — in a substation that supplied power to a hospital and ...more
|
 |
Connection or Bushing Problem?
Is this a connection or a bushing problem, or both?
Learn how to analyze images like this at an Infrared Training Center Thermography ...more
|
 |
Contactor
Left image shows heating from a loose contactor connection. The right image shows the system after repair.
|
 |
Coupling Misalignment
This is a double pump hydraulic system. Image 1 shows the coupling between the motor and 1st pump. Image 2 shows the coupling between 1st pump and ...more
|
 |
Drain Valve
Extraction Steam to High Pressure Heater Drain Valve
The higher temperature on the bypass valve indicates it may be leaking through. The ...more
|
 |
Duct Seal Pot
Infrared inspection shows a 650°F hot spot on the west side elevation lower duct to seal pot crotch weld area. External steam cooling is recommended ...more
|
 |
Filter capacitors
Overheating capacitors.
|
 |
Fluid Cooler
This is a heat exchanger that is used to cool fire resistant hydraulic oil. The oil is used to control a large governor valve position on a 660 MWatt ...more
|
 |
Freezer
Poor insulation in a walk-in cooler.
|
 |
Fuses
Hot fuse connection.
|
 |
Heater Shells
Internal refractory damage
|
 |
Heater tubes
This thermal image of horizontal tubes inside a gas-fired heater clearly reveals coke buildup in the center tubes.
|
 |
Injector
High injector temperatures can indicate plugging. A plugged injector will show very hot on an infrared scan. Pinpointing the problem before it ...more
|
 |
Line to line Jumper
Thermal Anomaly at bolted connection.
|
 |
Liquid Storage tank
Determination of liquid level.
|
 |
Main power transformer
Overheating contacts inside this load tap changer on a main power transformer has caused a dramatic increase in the temperature of the oil inside, ...more
|
 |
Mechanical and electrical equipment
The motor in the background is revealed by IR thermography to be much hotter than the one in the foreground,which is operating under similar load ...more
|
 |
Microcircuit
ThermaCAM image of a microcircuit showing 7 micron leads. Faults even smaller than 7 microns can be detected. ThermaCAM systems can measure very ...more
|
 |
Motor
Internal winding problem.
|
 |
Piping
IR camera assess the condition of dozens of vessels and miles of piping, all of which operate under extreme heat and pressure.
|
 |
Process lines
The cool areas where liquid has condensed inside this uninsulated vapor line are clearly shown in this thermal image (see second story on next page). ...more
|
 |
Pulley System
Hot drive belts.
|
 |
Pump Circuit Breaker
The heating on the C phase of this circuit breaker indicates a loose or bad connection.
|
 |
Refractory lined equipment
Furnace refractory breakdown a crude heater stack is clearly shown in this thermal image. unchecked, the condition can to accelerated metal ...more
|
 |
Substation
A wide view of a substation can quickly show areas where unwanted high resistance connections exist. Electrical current passing through a resistive ...more
|
 |
Transformer
Excess heat on this distribution transformer was attributed to internal damage plus low oil level.
|
 |
Transformer
Cold cooling fins due to low oil level in a transformer
|
 |
Transformer Radiators
This infrared image shows a cold radiator (lower left) possibly due to a bad pump.
This could be a serious problem as the capacity of the ...more
|
 |
Tubular bus
Bolted connection problem
|